A flue's job is simple to state and critical to get right: carry the products of combustion safely to outside air, so they never spill back into the room. When a flue fails, the danger is carbon monoxide — which is why flue inspection and testing sit at the heart of CCN1. This guide explains the types, where terminals can go, and the two tests you must know. It's revision material; only a Gas Safe registered engineer may work on a flued appliance.

Standard. Flueing for domestic appliances up to 70 kW net is covered by BS 5440-1. Terminal clearances and test methods come from it; manufacturer's instructions take precedence and the figures below should be confirmed against the current edition.

The three appliance/flue types

Where a terminal can go

A flue terminal must discharge where the products disperse safely and can't be drawn back into the building. BS 5440-1 sets minimum clearances from windows, doors, air vents, corners, eaves and the ground. Common figures to know (always verify against the current table and the MIs) include keeping a terminal at least around 300 mm from an openable window, door or air vent, and clear of internal/external corners. Any terminal within reach or below about 2 m from the ground should have a terminal guard to protect it and people from the hot surface.

Inspecting the flue

Before any test, look at the whole system: the right materials and size, sound joints, correct support, a liner where a masonry chimney needs one, a debris/catchment space where required, and no signs of staining, corrosion or blockage. A loose or disconnected connection on a shared/communal flue is Immediately Dangerous.

The flue flow test

The flue flow test proves the empty flue draws and is clear along its length, before you rely on the appliance. With the appliance off (or before it's connected), you introduce smoke (a smoke pellet) at the appliance position and watch that it's drawn up and discharges cleanly at the terminal, with none escaping back into the room. If it doesn't clear, the flue is blocked or not drawing and must be put right before going further.

The spillage test

The spillage test proves that, with the appliance actually running, the products go up the flue and don't spill into the room. The method in BS 5440-1:

  1. Run the appliance until it's up to temperature (about 5 minutes).
  2. Hold a smoke match at the edge of the draught diverter (or appliance spillage point) and watch that the smoke is drawn in, not pushed out.
  3. Repeat with any extract fans and the worst-case room conditions running (windows/doors shut, extractor on) — these can pull the flue into reverse.
  4. If spillage is detected, run on for a further 10 minutes and recheck; if it still spills, switch off, classify the fault and don't leave the appliance in use.
Why both tests. Flue flow proves the flue is clear; spillage proves the appliance in its real environment clears its products. A flue can pass flow yet spill once an extractor fan fights it — which is exactly the dangerous, CO-producing condition you're testing for.

Appliances in sleeping accommodation

An appliance with a rated input above 12.7 kW net (14 kW gross) installed in a bedroom or bed-sitting room must be room-sealed. Below that, a non-room-sealed appliance in sleeping accommodation must have an atmosphere-sensing device (ASD) that shuts it down before products build up. This is a favourite assessment point.

  1. Types: open-flued (Type B), room-sealed (Type C), flueless (Type A).
  2. Balanced flue: inlet and outlet in the same pressure zone; fanned flues allow longer runs.
  3. Draught diverter separates primary (below) and secondary (above) flue.
  4. Terminal: ~300 mm from openable windows/doors/vents; guard if below ~2 m — verify against BS 5440-1.
  5. Flue flow test: empty flue draws and is clear (smoke pellet).
  6. Spillage test: appliance running, smoke match at the draught diverter, repeated with extract fans on; recheck after 10 min.
  7. Sleeping accommodation: >12.7 kW net must be room-sealed; smaller non-room-sealed needs an ASD.

10-Question Mock Test

Click an option to see whether you got it right. Explanations appear instantly — no submitting at the end.

Your score: 0 / 10
Question 1 of 10
What is the danger when a flue fails to clear the products of combustion?
Question 2 of 10
A room-sealed (Type C) appliance:
Question 3 of 10
On an open-flued appliance, the draught diverter separates which two parts of the flue?
Question 4 of 10
When should a flue terminal be fitted with a guard?
Question 5 of 10
What does the flue flow test prove?
Question 6 of 10
During the spillage test, where do you hold the smoke match?
Question 7 of 10
Why repeat the spillage test with extract fans running and the room closed up?
Question 8 of 10
Spillage is detected. You run on a further 10 minutes and it still spills. What now?
Question 9 of 10
An appliance above 12.7 kW net is to go in a bedroom. It must be:
Question 10 of 10
You find a loose, disconnected connection on a shared communal flue. This is:

Flow test, spillage test, terminal clearances — get them automatic.

PlumbMate drills the flue details examiners love, with quizzes, flashcards and spaced repetition mapped to the gas ACS tickets.

🔒 PlumbMate Gas — coming soon

Full ACS revision — CCN1, CPA1, CKR1, HTR1 & CENWAT · £29.99/year · Launching soon

Prefer to browse first? Back to the Gas Blog →