Every wet central heating system you'll ever install falls into one of a small number of layouts. Get the differences straight and you'll understand every system schematic you meet on site — and you'll reliably pick up the exam questions that test whether you can tell one from another.

This post is the first in the Level 2 heating sub-cluster. For the others, see the boilers, controls, system layouts, open-vented vs sealed, and commissioning posts. For wider revision strategy, pair this with the spaced repetition guide.

Wet vs dry heating

Before the system types, the distinction you need to know first:

Everything in this post is about wet systems.

Full, background and selective heating

Three approaches to heating design — worth knowing because exam questions reliably test the distinction:

The main purpose in every case is thermal comfort — keeping the property warm enough for the people in it, regardless of how efficient the system is.

One-pipe systems

A one-pipe system uses a single continuous loop that acts as both the flow and the return. Hot water leaves the boiler, goes through or past a series of radiators, and returns to the boiler along the same pipe.

One-pipe central heating circuit diagram with radiators connected in series along a single flow loop

How it works:

The problem: cooler water coming out of each radiator mixes with the hot water in the main flow, so the radiators further along the loop receive cooler water than the first radiator.

Balancing: radiators at the end of the loop need to be oversized to give similar heat output to the first radiators on the circuit. This is the key one-pipe balancing fact.

One-pipe systems are not installed new today as they don't meet modern Building Regulation standards, but you'll meet them in older properties.

Two-pipe systems

The modern standard. In a two-pipe system, the flow and return are separate. Hot water leaves the boiler on the flow pipe, is forced through each radiator in parallel, and returns to the boiler through the separate return pipe.

Two-pipe central heating circuit diagram showing separate flow and return pipes serving each radiator

How it works:

Balancing is essential. Water takes the path of least resistance, so without balancing it would flow mostly through the radiators closest to the pump and barely reach the furthest ones. The fix: lockshield valves on one side of each radiator.

How the lockshield balancing works:

Closing the lockshields on near radiators increases resistance through them, forcing water out to the furthest radiators. When balanced correctly, all radiators heat up at similar rates.

Microbore

Microbore is a pipework variant rather than a different system type — it's still two-pipe in its design, but it uses very small-bore pipework to feed the radiators.

How microbore is laid out:

A manifold is a fitting that allows many small pipes to be connected to a main run. The advantage is neat, easier installation — all the small pipes run from one central point rather than snaking through the building. The disadvantage is that the small-bore pipes are easier to block with sludge, so regular system maintenance matters more.

Underfloor heating

Increasingly common in modern properties — either in parts of the house (typically kitchens and bathrooms) or throughout.

Underfloor heating layout diagram showing manifold, pipe loops in screed and blending valve arrangement

Key characteristics:

Can be wet (hot water through pipework laid in the floor, feeding into a manifold) or dry (electric heating mats). As plumbers, we're concerned with wet underfloor.

An important design point: you must not exceed the maximum flow temperature for the floor type — too much heat can damage certain flooring and cause discomfort.

Common exam traps

Trap 1: Confusing how one-pipe radiators are fed. One-pipe systems use convection through each radiator — hot water rises into the radiator, cooler water drops back into the loop. Two-pipe systems force water through the radiator. Questions often test which system uses which mechanism.

Trap 2: Lockshield balancing direction. Lockshields on the furthest radiators are fully open; the ones on the closest radiators are closed down. Get this the wrong way round and you starve the end of the circuit.

Trap 3: Microbore pipe sizes. 22mm to the manifold, 10mm or 8mm from the manifold to each radiator. The 22mm portion is normal two-pipe sizing; the small-bore is what makes it "micro".

Trap 4: Underfloor temperatures. Around 35°C up to max 60°C depending on floor. Don't confuse with traditional radiator temperatures (70°C+).

Quick revision summary

Before the mock test, six things you need to be able to produce from memory:

  1. Wet systems use water; dry systems use electrical elements
  2. Full / background / selective heating — the three design approaches
  3. One-pipe: single loop, water moves through radiators by convection, end radiators oversized to balance
  4. Two-pipe: separate flow and return, forced circulation, lockshield valves on one side of each radiator for balancing
  5. Microbore: 22mm to manifold, 10mm or 8mm from manifold to radiator
  6. Underfloor: low operating temperature (~35–60°C), even heat distribution, good match for heat pumps and condensing boilers

📝 10-Question Mock Test

Click an option to see whether you got it right. Explanations appear instantly — no submitting at the end.

Your score: 0 / 10
Question 1 of 10
What is the main objective of providing domestic central heating?
Question 2 of 10
A central heating circuit that has separate flow and return pipework is called a:
Question 3 of 10
In a one-pipe heating system, how does water travel through each radiator?
Question 4 of 10
The main disadvantage of a one-pipe circuit in a central heating system is that:
Question 5 of 10
In a two-pipe system, which valves are used on one side of each radiator for balancing purposes?
Question 6 of 10
In a two-pipe system, lockshield valves on the radiators furthest from the pump should be:
Question 7 of 10
Which of the following heating systems uses a manifold to feed multiple small-bore pipes from a main run?
Question 8 of 10
What is the typical pipe size feeding individual radiators from a microbore manifold?
Question 9 of 10
Which of the following is an advantage of underfloor heating?
Question 10 of 10
Compared with a traditional radiator system, underfloor heating operates:

How PlumbMate puts this into practice

System-type questions are exactly what PlumbMate drills you on — with the spaced repetition engine making sure the distinctions stay clear.