Open vented hot water is the traditional UK domestic hot water setup: a cylinder in the airing cupboard, a cistern in the loft, gravity pressure, and a collection of specific pipework rules that students reliably find overwhelming on first encounter. Learn them properly and every diagram question about an open vented system becomes straightforward — the rules are specific and testable, but there aren't that many of them.

This is the third post in the Level 2 hot water sub-cluster. For the others, see the classifications, cylinder types, unvented systems, heat sources and temperature control posts.

What makes a system "open vented"

The defining feature: the system is open to the atmosphere through a vent pipe that rises up and over the cold water storage cistern. Water can expand into and out of the cistern as it heats and cools. Pressure in the system is set by gravity — the height of the cistern above the outlet determines the pressure at that outlet.

Diagram showing the cold water storage cistern (CWSC) feeding the hot water cylinder, with a separate F&E cistern feeding the primary heating circuit

Key consequences:

Cistern sizes

The CWSC that feeds an open vented hot water system has specific minimum sizes depending on what it feeds:

Or the same capacity as the cylinder if a cylinder larger than 110 litres is installed — the cistern must be able to refill the cylinder in a single draw-off without running dry.

Key pipes in an open vented indirect system

An open vented indirect hot water system has four key pipes you need to identify and size:

Open vented hot water system diagram with the four key pipes labelled A to D — the secondary cold feed, secondary open vent, primary cold feed and primary open vent

1. Secondary cold feed (CWSC to cylinder)

The pipe that fills the cylinder with water from the CWSC and accommodates expansion back up into the cistern during normal operation.

2. Secondary open vent (cylinder to over CWSC)

The pipe from the top of the cylinder that rises over the CWSC and terminates above it. Serves as the pressure relief for the secondary (drinking water) side.

Why the 450mm horizontal run? Water in the cylinder forms temperature layers — hottest at the top, coolest at the bottom. This is called stratification. Without the 450mm horizontal run, the hot water at the top of the cylinder would rise up the vent, cool, and fall back down — a phenomenon called parasitic circulation. The horizontal run forces the hot water to stop rising before it can enter the vent properly, preventing this.

3. Primary open vent (boiler flow to over F&E cistern)

Only present on indirect systems (where there's a boiler heating the primary circuit).

4. Primary cold feed (F&E cistern to primary circuit)

Only present on double feed indirect systems.

A useful memory aid: the vents and primary cold feed are all safety/expansion routes, and none of them can have valves. The only secondary-side pipe that takes a valve is the secondary cold feed (which needs a service valve for cylinder maintenance).

Vent pipe rise calculation

The secondary open vent doesn't rise to an arbitrary height — it has a specific required minimum rise above the water level in the cistern, based on the height of the cistern above the cylinder.

Open vented hot water and central heating system diagram with the minimum pipe sizes and vent rise dimensions labelled

The formula:

Rise (metres) = 0.04 × height in metres + 0.15

where "height" is the vertical distance from the top of the water in the cistern down to the top of the cylinder.

Worked example: if the CWSC is 5m above the cylinder, the vent must rise:

For a 10m head (the maximum for a Grade 3 cylinder — see below), the vent rise is:

The formula accounts for the fact that heated water expands — the taller the system, the more the water can push up the vent as it heats. The vent rise has to exceed that push, or water would spill into the cistern every time the cylinder heats up.

Cylinder grades (working head)

Open vented cylinders are classified by the maximum pressure (head of water) they can handle:

Grade 3 is by far the most common domestic cylinder because a typical UK house rarely has more than 10m of head between the cistern in the loft and the lowest outlet on the ground floor. Installing a Grade 1 or Grade 2 cylinder where Grade 3 would work is unnecessarily expensive.

For head calculations, remember from the plumbing science unit: 1 metre of water head = 0.1 bar. So Grade 3's 10m maximum head equals 1 bar of static pressure at the lowest point.

Stratification

Hot water in a cylinder forms layers of different temperature:

This is called stratification and it's the reason hot water cylinders work effectively. Heat transfers up (hot water rises due to lower density), so the top of the cylinder stays hot even when cold water enters the bottom to refill what's been used. When you open a hot tap, you draw from the hottest layer at the top.

Key installation consequences of stratification:

Parasitic circulation

Parasitic circulation is the phenomenon where hot water rises up the vent pipe, cools at the top, falls back down, and circulates continuously — wasting heat from the cylinder.

Hot water cylinder diagram showing one-pipe parasitic circulation, where hot water rises up the connection, cools, and falls back continuously — wasting heat from the stored hot water

Without prevention, parasitic circulation happens because:

  1. Hottest water sits at the top of the cylinder
  2. The vent pipe connects at the top
  3. Hot water naturally rises up the vent
  4. At the vent's high point, it cools
  5. Cooled, denser water falls back down into the cylinder
  6. More hot water rises to replace it
  7. The cycle continues indefinitely, pulling heat out of the cylinder

The prevention: 450mm horizontal run. By forcing the vent pipe to run horizontally for at least 450mm before rising, parasitic circulation is broken. Hot water can't rise through a horizontal pipe, so it doesn't climb the vent under normal conditions.

Pipework insulation

Part L of the Building Regulations requires:

This prevents heat loss from the pipework around the cylinder and supports stratification (uninsulated pipes lose heat, which cools the top layer of water and disrupts stratification).

Additionally, pipework should slope upwards towards the CWSC from the cylinder to minimise airlock risk — trapped air can escape upwards into the cistern rather than being stuck in the pipework.

Cold feed above cold distribution (scald prevention)

A best-practice rule from the cold water cistern regulations that matters for hot water installation:

If the CWSC feeds both the hot water cylinder AND the cold water outlets, the cold feed pipe (to the cylinder) should connect ABOVE the cold distribution pipe (to the cold outlets).

Reason: if the mains water supply to the cistern fails and the cistern drains, the hot water will run out FIRST (the higher-connected cold feed stops working first), leaving cold water at the taps. This prevents a scalding risk where the taps could otherwise deliver superheated water with no cold water to mix with.

Common exam traps

Trap 1: Secondary vent horizontal run. At least 450mm of horizontal run before the vent rises. Not 300mm, not 600mm — specifically 450mm minimum.

Trap 2: Vent rise formula. 0.04 × height + 0.15 (both in metres). Worth memorising the formula rather than trying to derive it.

Trap 3: Cylinder grades and domestic use. Grade 3 (10m max head) is the most common domestic. Students sometimes assume Grade 1 because it's the "highest" rating — it's overkill for typical UK homes.

Trap 4: No valves on vents or primary cold feed. Only the secondary cold feed takes a valve. Vents are safety pipes; primary cold feed is an expansion route; all three must be unobstructed.

Trap 5: Cistern sizes. 110 litres for cylinder only; 220 litres if feeding hot + cold; or same as cylinder capacity if cylinder > 110L.

Trap 6: 1m insulation before and after cylinder. Part L requirement. Not optional. Not "where practical". One metre.

Trap 7: Parasitic circulation prevention. The fix is the 450mm horizontal run, not insulation alone, not a valve on the vent. The horizontal run breaks the convection current.

Quick revision summary

Before the mock test, eight things you need to be able to produce from memory:

  1. Cistern sizes: 110L (cylinder only), 220L (hot + cold), or same as cylinder if >110L
  2. Four key pipes: secondary cold feed (22mm), secondary open vent (22mm / 19mm ID min), primary open vent (22mm), primary cold feed (15mm)
  3. Secondary vent: 450mm horizontal run before rising; no valves; offset at cylinder to prevent one-pipe circulation
  4. Vent rise formula: 0.04 × height in metres + 0.15
  5. Cylinder grades: Grade 1 = 25m, Grade 2 = 15m, Grade 3 = 10m (most common domestic)
  6. Stratification: hot at top, cold at bottom; stratification supports cylinder efficiency
  7. Parasitic circulation prevented by the 450mm horizontal run
  8. Insulation 1m before AND after cylinder (Part L)

📝 10-Question Mock Test

Click an option to see whether you got it right. Explanations appear instantly — no submitting at the end.

Your score: 0 / 10
Question 1 of 10
What is the minimum size of a cold water storage cistern feeding an open vented hot water cylinder only?
Question 2 of 10
What is the minimum cistern capacity if it feeds both the hot water cylinder and the cold water outlets in an indirect cold water system?
Question 3 of 10
What is the minimum size of the secondary cold feed pipe from the CWSC to an open vented hot water cylinder?
Question 4 of 10
The secondary open vent pipe from the top of a hot water cylinder must run horizontally for at least what distance before rising?
Question 5 of 10
Using the formula 0.04 × height + 0.15, what is the minimum vent pipe rise (in metres) above the cistern water level if the CWSC is 6 metres above the cylinder?
Question 6 of 10
Open vented hot water cylinders are rated by working head. Which grade is most commonly used in domestic properties?
Question 7 of 10
The phenomenon where water in a cylinder forms temperature layers (hottest at top, coolest at bottom) is called:
Question 8 of 10
What problem is prevented by fitting the secondary open vent with a 450mm horizontal run before it rises?
Question 9 of 10
How far should pipework going into and out of a hot water cylinder be insulated, in accordance with Building Regulations Part L?
Question 10 of 10
Which of the following pipes on an open vented indirect hot water system must NOT have any valves fitted?

How PlumbMate puts this into practice

Open vented hot water pipework is heavy on specific figures — ideal for spaced repetition.