Parts-swapping is expensive, and it usually leaves the real fault in place. This module is about the alternative: a repeatable method that starts with the customer's account and ends with a proven cause. Most of it rests on one thing — a commissioning record with measured values on it, which is why the previous module laboured that point so hard.

This covers Module 7 of the PlumbMate heat pumps course: the fault-finding method, routine servicing, water-side and source-side diagnosis, refrigerant leaks, and re-commissioning after a repair. There is a 10-question mock test at the end.

The fault-finding method

The method for finding a fault on a heat pump
A fault code names a symptom, not a part.
  1. Gather information. What is the reported symptom, when does it occur, and what changed just before it started? Customers frequently tell you the answer without realising — “it has never been right since someone adjusted it” is a diagnosis.
  2. Verify the symptom. Confirm that what was reported is what is actually happening.
  3. Read the fault code and consult the manufacturer's schematics. Fault codes are manufacturer-specific — the same number means entirely different things on different makes.
  4. Compare against the commissioning record. This is what turns a reading into information.
  5. Test to prove the cause before replacing anything.

Why the commissioning record matters so much

Without a baseline, a flow temperature of 52 °C or a ΔT of 8 K is just a number. Against a record showing 45 °C and 5 K, the same readings say something has changed — a setting altered, a filter blocking, a pump slowing. It converts guesswork into comparison.

Four documents should be to hand: the manufacturer's service schedule, the commissioning record, previous service records, and the system schematic. The commissioning record is the one most often missing and the one that makes diagnosis quickest.

Resetting is not fixing

A reset clears the symptom without addressing the cause, and the fault returns. A pressure lockout in particular is a protective device doing its job — the question is why it tripped, not how to clear it.

Listen to the customer, read the code, compare with the baseline, then test. Replace last, not first.

Routine servicing

Servicing splits neatly into two halves, plus two extra checks on ground source. The sealed refrigerant circuit is checked for signs of leakage but not routinely opened — that is F-Gas work.

Air side

Water side

Ground source additions

Two more, both indirect because the array is buried: brine circuit pressure against the commissioning baseline, and antifreeze concentration by refractometer. A falling pressure points to a leak in the array; weakening concentration risks ice in the evaporator.

Record the readings, not just the visit

“Serviced, all OK” records nothing. Individual readings mean little; the sequence means a great deal. A ΔT creeping from 5 K to 6 K to 8 K across three services describes a circuit slowly restricting, and it can be dealt with cheaply. Noticed only when it locks out on high pressure, the same problem is a callout and possibly a damaged component.

The single most useful rule in heat pump diagnosis

Before the detail, learn this, because it sorts most faults into the right half of the machine immediately:

High pressure sends you to the water side. Low pressure sends you to the source side.

The heat pump takes heat in at the evaporator and rejects it at the condenser. If it cannot reject what it makes, condensing pressure climbs and it trips on high pressure — a water-side problem. If it cannot absorb enough, evaporating pressure falls and it trips on low pressure — a source-side problem. Keeping the two sides separate in your head is most of the skill.

Diagnosing water-side faults

The signature: wide ΔT plus high-pressure lockout

A temperature difference far wider than design means the flow rate has fallen. With too little water passing through the condenser, heat cannot be carried away, condensing pressure climbs, and the unit protects itself.

Check in order of likelihood: blocked magnetic filter first — commonest and quickest to eliminate — then a partially closed valve, then a failing or wrongly set pump, then undersized pipework.

Cycling in mild weather

Frequent starting and stopping in mild weather is the signature of an output-versus-volume mismatch. Demand is at its lowest, so an oversized unit — or one whose emitters have largely closed off — puts in more heat than the system can absorb.

A common version: another trade fits TRVs throughout. As the valves close they cut both the water in circulation and the surface available to give off heat, and the system starts cycling. The fix is volume, better modulation, or a control strategy that keeps a path open.

Reason from what works

This is the habit that separates a diagnostician from a parts-swapper. If hot water is satisfactory but the radiators stay cold, the heat pump is clearly making heat. The fault is therefore in what happens to that heat afterwards — most likely a diverter valve stuck in the hot water position, or not receiving its call for heating. A failed compressor would have taken out both.

Equally, a fault affecting one room only must lie in that room's circuit or emitter: a balancing problem, a closed valve, an air lock, or an emitter that was never large enough for the room's heat loss.

Pressure loss

A sealed system should not lose water. Repeated topping up introduces fresh oxygenated water and dilutes the inhibitor, so corrosion accelerates. Find the loss — a weeping joint, a discharging relief valve, or a failed expansion vessel forcing water out through the relief. Check the relief discharge for evidence.

The immersion running constantly

An immersion heater runs at a COP of 1, so anything driving it wrecks running costs. Investigate why the heat pump is not satisfying hot water demand: a cylinder setpoint above what the unit can reach, an undersized or fouled coil, a pasteurisation cycle set too frequently, or a diverter fault. Check the settings first — they cost nothing to correct.

Diagnosing air-side and source-side faults

Air source: persistent icing

Heavy ice that the defrost cycle is not clearing has three plausible causes, all on the air side:

Note what is not a cause: inhibitor concentration, system pressure, or anything else on the water side.

Ground source: low pressure and a falling brine pressure

Low-pressure trips with a brine pressure below the commissioning figure point to a loss from the sealed loop — which on a buried array means a leak. Use the manifold to isolate and test circuits individually; it is the only access point a buried array has. Air trapped in the array produces similar symptoms without any leak, so check the purge before assuming the worst.

Noise

Follow the evidence to where the noise actually is. A whine traced to the fan assembly, with no fault codes displayed, means the control system sees nothing electrically abnormal — so look at the mechanical and airflow condition: clearances against the manufacturer's figures, obstructions, debris in the coil, or a fan or mounting defect.

Poor performance with no fault at all

Sometimes nothing is broken. Check the current control settings against the commissioning record — a compensation curve altered after a power cut, or a customer who has been switching the system off overnight, will produce exactly the complaint of a system that “never gets warm”.

Refrigerant leaks

Immediate actions, in this order

Do not keep the system running to disperse the leak. That releases more refrigerant, which is both a hazard and an offence under the F-Gas Regulations.

Who may repair it

Work on refrigerant circuits requires an F-Gas handling qualification. If you do not hold it, your role is to make the situation safe, isolate the system, inform the customer, and arrange for a qualified engineer.

That is not a limitation to apologise for. Recovering and recharging without the qualification is unlawful regardless of technical ability, and knowing where the line sits is professional judgement rather than a shortcoming.

Never top up and walk away

Recharging without finding the leak means the new charge escapes as well. It is an offence, it is a waste, and it leaves the customer with the same fault in six months.

The F-Gas Regulations require records of refrigerant quantities recovered, added and lost. Beyond compliance, those records have diagnostic value: a system topped up twice in two years has a leak nobody has properly found, and the paperwork is what reveals the pattern.

Ventilate, no flames, isolate, report. Then hand it to someone qualified.

After rectification: re-commissioning and records

Two things must follow every repair

Do not reset all controls to factory defaults to “clear any residual errors”. That destroys the commissioned configuration and creates a new problem in place of the old one.

What goes in a service record

The date, the checks carried out, the readings obtained, any parts fitted, any defects found, and when the next service is due. Recording only defects loses the readings that would have shown a developing problem before it became a defect.

When to escalate

Competence and authorisation set the boundary. Refrigerant circuit work needs F-Gas qualification; some diagnostics need manufacturer-specific tools or software; warranty conditions may require an approved engineer. Escalate when the fault lies beyond that boundary — not immediately on arrival before any investigation, and not after replacing every component in turn.

What to tell the customer

Between visits they can usefully check anything visible and safe: the pressure gauge, that nothing is blocking the outdoor unit, that the drainage route is clear, and that the system is behaving as it normally does. A customer who notices a falling gauge early saves themselves a corroded system.

Anything requiring tools, isolation or panel removal belongs to the engineer. Never suggest a customer opens the unit.

The diagnostic shortcuts worth memorising

SymptomPoints to
High-pressure lockoutWater side — it cannot reject its heat
Low-pressure lockoutSource side — it cannot absorb enough heat
Wide ΔTLow flow: filter, valve, pump, pipework — in that order
Hot water fine, heating coldDiverter valve or the heating call — the machine is making heat
One room coldThat room's circuit or emitter, never the heat pump
Cycling in mild weatherOutput versus volume mismatch
Persistent icingDrainage, airflow, or the defrost cycle — all air side
Falling brine pressureLeak in the array — but rule out trapped air first
Immersion running constantlyCheck the settings before anything else
Repeated topping upA leak, plus diluted inhibitor and accelerating corrosion

That is the whole course

Seven modules, and every one of them comes back to the same two ideas: temperature lift decides efficiency, and the record you leave is what makes the next visit possible. If you have read the series from Module 1 through to here, you have covered the ground a heat pump installer is expected to know.

📝 10-Question Mock Test

Click an option to see whether you got it right. Explanations appear instantly — no submitting at the end.

Your score: 0 / 10
Question 1 of 10
Why is the commissioning record the most valuable document when diagnosing a fault?
Question 2 of 10
A unit has tripped on high pressure. The customer has already reset it twice and it keeps returning. What does that tell you?
Question 3 of 10
A heat pump trips on <em>low</em> pressure. Which side of the system should you investigate?
Question 4 of 10
A system shows a ΔT far wider than design and is tripping on high pressure. What should you check first?
Question 5 of 10
Hot water is satisfactory but the radiators stay cold. What does that rule out, and what does it point to?
Question 6 of 10
A system cycles frequently in mild weather. What is the usual cause?
Question 7 of 10
An air source unit has heavy ice the defrost cycle is not clearing. Which is <em>not</em> a plausible cause?
Question 8 of 10
What must be done before cleaning an outdoor unit's coil?
Question 9 of 10
You suspect a refrigerant leak in an enclosed plant space. What are the first two actions?
Question 10 of 10
After completing a repair, which action is wrong?

Finish the job on the PlumbMate heat pumps course

Fault finding is a skill you build by doing it repeatedly against realistic symptoms. The heat pumps course gives you: