The most common reason an unvented installation ends with an unhappy customer is not the cylinder. It is the main feeding it — and that is a measurement you take before you quote, not an assumption you make afterwards.

The short answer

An unvented system needs pressure and flow, independently. As a working figure, look for about 1 bar and 20 litres per minute; the specific minimum for a given unit comes from the manufacturer's installation instructions. Confirm it with a flow meter at the cold water service connection to the unit — not at a garden tap on a different branch.

7.5 bar at 5 litres a minute is not a usable supply. Five litres a minute will not run a shower whatever the pressure, and 7.5 bar is above the maximum inlet pressure of most units anyway. That single example is the whole point: the two figures do not substitute for one another.

Then three installation rules carry most of the marks: hot water must reach the outlet above 50 °C within one minute, insulation is required beyond a table of lengths that tighten as the pipe gets bigger, and the discharge pipe D2 goes up one size for every 9 m of equivalent resistance.

Static and dynamic pressure

Pressure and flow figures for an unvented hot water installation
Static pressure tells you very little. The dynamic figure is what the system runs on.
Key figures for installing hot water
The examinable numbers from this article, in one place.

Pressure comes in two forms and only one of them is worth designing around.

A house showing 2 bar static may drop below 1 bar dynamic on a busy evening, which is the difference between a system that works and one you get called back to. Take the reading when the street is using water, not at ten in the morning when nobody is home.

When the supply is not good enough

Two remedies exist and they are often used together.

On an accumulator installation two pressure reducing valves are usually fitted: the first controls the pressure entering the property, the second reduces it to the figure the cylinder manufacturer requires. A pressure reducing valve is the type in which back-pressure in the valve chamber acts across the full diaphragm to close it, which is what gives it close control of its outlet pressure.

The order of the inlet group

On an unvented unit the incoming order is examinable and it does not vary:

cold water supply → stop valve → in-line strainer → pressure reducing valve → single check valve → expansion vessel connection → expansion (pressure) relief valve → cylinder

The balanced cold connection is taken off after the pressure reducing valve, so that blended outlets see equal pressures on both sides. Take it off before the PRV and every shower in the house becomes a temperature fight.

Pipe sizes, materials and routing

Sizes are set by what the vessel needs. Unvented systems normally need at least a 22 mm cold feed from the undertaker's supply, because of the flow rate they work at, and a 22 mm hot draw-off, reduced for individual appliances such as basins, sinks and bidets.

Materials are copper to BS EN 1057 or polybutylene. The pipework must withstand at least 1½ times the normal operating pressure and sustained temperatures of 95 °C with occasional excursions to 100 °C.

Route the pipes so hot pipework does not warm cold pipework running alongside it — the Water Regulations require cold water not to be warmed above 25 °C so far as is reasonably practicable. And allow for expansion where pipes pass through walls and floors, or the installation will tick and creak: polybutylene expands about 0.00018 m per metre per degree, copper about 0.000016 m.

The electrical connection, and proving the work

The final connection to an immersion heater is made in heat resistant flexible cable. Size the protective device from the load: a 6 kW heater on 230 V draws about 26 A, so a 32 A Type B circuit breaker is the suitable rating.

Soundness is proved by a hydraulic test with water at 1.5 times the maximum working pressure — not an air test. Take care not to exceed the pressure an open vented cylinder can stand; if necessary disconnect it and cap the pipework before testing.

Dead legs, and the one-minute rule

A customer in a long bungalow runs the en suite basin tap for half a minute before anything warm arrives. That is a dead leg: cold water standing in a hot pipe between uses, run to waste every time. It is a fault of design, and there are only two remedies.

BS 8558 clause 4.3.5.1.1 says hot water should reach the outlet at or above 50 °C within one minute of running the water, and the same applies to the supply feeding a thermostatic mixing valve. That one figure limits dead leg length and pipe size at once, because an oversized draw-off holds more cool water per metre that has to be run off first.

Dead legs should be insulated and as short as practicable, and on a secondary circulation system a dead leg should not exceed a volume of 0.5 litres.

Which pipes must be insulated

The guidance to the Water Regulations requires, as the withdrawn BS 6700 (clause 5.9.3.1) did, that hot pipes to a tap longer than the lengths below are insulated — and that all fittings forming part of a primary or secondary circulation system are insulated whatever their length.

Outside diameterMaximum uninsulated length
12 mm20 m
Over 12 up to 22 mm12 m
Over 22 up to 28 mm8 m
Over 28 mm3 m

The limit tightens as the pipe gets bigger, because a bigger pipe holds more standing water per metre — so it earns fewer metres. Note the sizes are outside diameters.

The compliance guidance under Part L adds the practical rules: primary circulation pipes for domestic hot water are insulated throughout their length; all pipes connected to a hot water storage vessel — including the vent pipe — are insulated for at least 1 metre from the vessel or to where they become concealed; and where secondary circulation is used, all pipes kept hot by it are insulated.

Besides saving energy, insulation keeps the distribution above 50 °C at the outlets and the return at 50 °C or more (55 °C in healthcare). It is a legionella control measure as much as an efficiency one — which is the version of the argument that persuades a customer unmoved by pence.

When a secondary loop is justified

A secondary circulation loop is justified where the run is too long for the dead leg limits, or where the 50 °C-in-a-minute figure cannot otherwise be met. It is not free: a pump runs, a circuit loses heat continuously, and the return must come back at 50 °C or more (55 °C in healthcare). The withdrawn BS 6700 (clause 5.3.8) put it bluntly, and it still holds — secondary circuits inevitably dissipate heat and should be avoided where they can be.

Installing it:

The alternative to a loop altogether is electric self-regulating trace heating under the insulation, maintaining at least 50 °C and removing the dead leg without a return pipe.

The four temperatures

Four numbers run through every hot water system. Only the bath limit is regulation, in Approved Document G; the other three are HSG274 Part 2 and BS 8558 guidance, and you work to all four:

The logic is a chain: store hot enough to be safe from bacteria, distribute hot enough to stay that way, deliver cool enough to be safe from scalding. The first two come from legionella control; the third from Approved Document G paragraph 3.65, which limits hot water supply to a bath to 48 °C by an in-line blending valve or other temperature control device with a maximum temperature stop.

The device that reconciles them is the thermostatic mixing valve — and understand exactly what it does. It protects against scalding. It does nothing about bacteria. Keeping the store hot is what controls the bacteria; the valve simply makes the delivered water safe to touch. Where communal showers serve schools or the public, the Water Regulations guidance puts the discharge limit at 43 °C.

Controlling the stored temperature, in tiers

Stored water must never exceed 100 °C. Three devices operate in order as the temperature rises:

  1. A thermostat set to the working temperature. On a cylinder heated directly by an immersion heater, the immersion's own thermostat is the component that controls the temperature of the hot water — typically adjustable between 50 and 70 °C.
  2. A second, high limit thermostat or energy cut-out, independent of the first, which cuts the supply if the working thermostat fails. Manually resettable, or non-resettable and requiring the heater to be replaced.
  3. On an unvented vessel, a temperature and pressure relief valve as the last line, fitted directly on the vessel so stored water cannot exceed 100 °C.

Sizing the discharge pipework

An unvented unit carries an expansion (pressure) relief valve and a temperature and pressure relief valve. Both discharge through a short metal pipe, D1, into a tundish.

The tundish is vertical, in the same space as the cylinder, within 600 mm of the valve outlet, and it exists so a discharge from either valve is visible. D1 must be at least the nominal outlet size of the safety device.

From the tundish, D2 falls to a safe outside termination, with 300 mm vertical below the tundish before any bend and then a continuous fall of at least 1 in 200. Its size comes from Approved Document G Table 1:

Minimum D1D2 sizeMaximum straight length
15 mm22 mm9 m
15 mm28 mm18 m
15 mm35 mm27 m

The rule underneath the table: D2 is one size larger than the valve outlet for up to 9 m of equivalent resistance, two sizes for 9 to 18 m, three sizes for 18 to 27 m, and so on. Bends count: each 22 mm elbow is 0.8 m, each 28 mm elbow 1.0 m.

Worked example

A G½ valve with a 15 mm D1, and a D2 run of 7 m with four 22 mm elbows.

A 28 mm D2 is satisfactory. Notice the elbow allowance changes with the pipe size — work it in the size you are testing, not the size you started with.

One practical rule to close on. If an expansion vessel fails and a replacement has to be ordered, isolate the system and temporarily decommission it so it cannot be used until the vessel is replaced; where pipework is left open, cap the ends off.

🔢 The numbers worth memorising

Unvented supply, working figure
about 1 bar and 20 l/min
Where you measure it
flow meter at the cold service connection to the unit
Accumulator replenishment
around 2 bar incoming
Pump direct off the main
maximum 12 l/min
Unvented pipe sizes
22 mm cold feed, 22 mm hot draw-off
Pipework rating
1½ × operating pressure, 95 °C sustained
Cold water not warmed above
25 °C
6 kW immersion on 230 V
about 26 A — a 32 A Type B breaker
Soundness test
hydraulic, 1.5 × maximum working pressure
Hot at the outlet
above 50 °C within one minute
Uninsulated hot pipe (OD)
12 mm 20 m, 22 mm 12 m, 28 mm 8 m, over 28 mm 3 m
Pipes at a storage vessel
insulated 1 m from the vessel, vent pipe included
Dead leg on a secondary system
no more than 0.5 litres
The four temperatures
store 60, outlet 50+, return 55, bath 48 °C max
Communal shower discharge
43 °C
Tundish
vertical, same space, within 600 mm of the valve
D2 fall
300 mm vertical before any bend, then 1 in 200
D2 sizing
one size per 9 m of equivalent resistance
Elbow allowance
0.8 m at 22 mm, 1.0 m at 28 mm

⚠️ Where people go wrong

  • Reading pressure and assuming flow. 7.5 bar at 5 l/min is unusable — the two figures never substitute for one another.
  • Taking the reading at a garden tap, or at ten in the morning. Measure at the unit’s own connection, at peak.
  • Quoting static pressure as the design figure. Dynamic is what the system actually gets.
  • Taking the balanced cold before the pressure reducing valve. Every blended outlet then fights itself.
  • Air-testing an unvented installation. Soundness is hydraulic, at 1.5 × working pressure.
  • Reading the insulation table as inside diameter. The lengths are by outside diameter.
  • Assuming a short pipe on a circulation system escapes insulation. On a primary or secondary circuit, every fitting is insulated whatever its length.
  • Fitting a cast iron circulator to a secondary loop. It carries potable water — bronze or stainless only.
  • Believing a TMV controls legionella. It protects against scalding and nothing else.
  • Sizing D2 off straight length alone. Each bend eats 0.8 or 1.0 m, and the allowance changes with the size you are testing.

📝 10-Question Self-Test

Straight from the Level 3 course question bank. Click an option to see whether you got it right — the explanation appears instantly, and there is nothing to submit.

Your score: 0 / 10
Question 1 of 10
Where the minimum D1 discharge pipe size is 15mm, how long can a straight run of 28mm D2 discharge pipe from the tundish be at most?
Question 2 of 10
Why is the component shown fitted?
The drawing this question refers to
Question 3 of 10
With a minimum discharge pipe size of 15mm, what is the longest straight run permitted for a 22mm D2 discharge pipe from the tundish?
Question 4 of 10
The component shown in the image is fitted to do what?
The drawing this question refers to
Question 5 of 10
Back-pressure in the valve chamber acting across the full diaphragm closes which type of valve, giving close control of its outlet pressure?
Question 6 of 10
Whenever hot water is drawn from the taps, a creaking sound comes from beneath the timber floor of a house. What is the most likely reason?
Question 7 of 10
For an uninsulated 22mm hot water pipe, what is the longest dead leg permitted, in metres?
Question 8 of 10
Which one of these incoming supply pressure and flow rate combinations would generally NOT be suitable for the successful operation of an unvented hot water storage system?
Question 9 of 10
What is the principal design reason for sizing the pipework of a hot water system?
Question 10 of 10
An open vent from a vented primary circuit must rise above the overflow level of the feed and expansion cistern. How is the correct height worked out?
← Previous in Hot water systemsThe Documents, the Demand, and Every Hot Water Calculation Worked Through Next in Hot water systems →Inspecting, Testing, Flushing and Disinfecting a Hot Water System

Going further: the lessons behind this article

This article is the public answer. Unit 332 of the Level 3 course takes the same ground to the depth the exam and the synoptic assignment ask for, in 3 lessons:

  • Supply pressure and flow, and where the pipes run
  • Insulation, dead legs and secondary circulation
  • Temperature control, outlets and safety relief pipework