Everything about the hazard came down to one sentence: the danger is heat, not pressure. So the protection is three temperature devices, each set above the one before it, and each doing its work only if the one before has failed.

The short answer

Approved Document G 3.17 requires an unvented hot water storage system to have a minimum of two independent safety devices, in addition to any thermostat provided to control the desired temperature. Add the thermostat back in and you have the three-tier chain taught on site.

DeviceOperates atWhat it does
Control thermostat60 to 65 °CHolds the store at its working temperature
Overheat thermostat (energy cut-out)about 85 °CCuts off the heat source and stays off until reset by hand
Temperature relief valve90 to 95 °C, full bore by 95Discharges the hot water to a safe place

Every setting sits below 100 °C, and that ceiling is the whole point — Schedule 2 paragraph 18 requires the temperature in a secondary hot water system not to exceed it. Paragraph 23 requires a temperature relief valve, or a combined temperature and pressure relief valve, on every unvented vessel with a capacity greater than 15 litres, located directly on the vessel.

How each tier works

A temperature and pressure relief valve with its probe
The probe sits in the stored water. Factory fitted, and never relocated.
The three tiers of thermal protection on an unvented cylinder
Functional or safety? That is the line examiners test, and the thermostat is on the wrong side of it.
Key figures for three levels of safety, and the discharge pipe that has more rules than any other
The examinable numbers from this article, in one place.

The control thermostat is a functional control. On a directly heated vessel it is the immersion heater's user thermostat; on an indirectly heated vessel it is the cylinder thermostat, wired to the heating wiring centre, and the component it switches is the motorised valve on the primary circuit.

The overheat thermostat, or non-self-resetting thermal cut-out, is the second fail-safe. On a direct system it is built into the immersion heater. On an indirect system it is a separate component wired to shut the boiler down or close the motorised valve — a linked arrangement serving both the vessel and the boiler, and the cut-out may be on the boiler itself. If the electrical supply is disconnected, the device must operate to interrupt the heat, and each heat source has its own cut-out.

So on an indirect cylinder whose stored water passes 85 °C, the correct answer is that the high limit thermostat operates the motorised valve to cut off the primary heat supply.

The temperature relief valve is the third fail-safe. It is factory fitted directly on the storage vessel and must not be relocated to any other fitting. It closes automatically after discharging, and it carries a manual test lever so it can be lifted at each service to prove it opens and reseats. The expansion relief valve has easing gear too, a twist cap, so both relief valves are tested the same way.

Functional or safety? The line examiners test

Functional controls: line strainer, pressure reducing valve, single check valve, expansion vessel or expansion valve, and the control thermostat. They keep the system working day to day and protect the supply. The expansion valve is listed here, although its job is safety: it lets out excess pressure if the vessel or the reducing valve fails.

Safety devices (the two Approved Document G requires): the non-self-resetting thermal cut-out and the temperature relief valve. They protect the user, and act only when the functional controls have already failed.

If you are unsure which a component is, ask what happens without it. If the system works badly, it is functional. If nothing happens until the day it matters, it is a safety device — and safety devices are never optional, never bypassed and never substituted with the wrong part.

One fault follows straight from the sequence. A customer reports the hot taps have gone cold and stayed cold: the normal temperature control has failed (the thermostat, or a motorised valve stuck open), letting the store overheat, and the non-self-resetting cut-out has tripped and will stay off until someone resets it by hand.

D1: valve to tundish

Discharge pipework from a relief valve: D1 no more than 600 mm to the tundish, at least 300 mm straight down below it, then D2 falling at least 1 in 200 to a safe termination, with the D2 sizing table
D1 is short and steep to the tundish. D2 is long and shallow to a safe termination.

Relief valves do not trickle. They discharge a fast flow of water at close to boiling. The discharge pipework has one job: get that water out of the building without hurting anybody, and let somebody see that it happened.

D1 is the short length of metal pipe from the temperature relief valve to the tundish, and it connects straight onto the valve. Its size is not less than the nominal outlet size of the safety device — so a G½ valve gets 15 mm D1.

The tundish

Discharge pipework figures for D1, the tundish and D2
D1 is short and steep. D2 is long and shallow. The tundish sits between them, visible.

The tundish sits between D1 and D2 and does three things: it gives a visible sign that a relief valve is discharging; it provides the air gap the Water Regulations require between the discharge pipework and the relief valves; and it gives the water somewhere to escape if the pipe below is blocked.

It must be vertical, in the same space as the cylinder, as close as possible to and lower than the safety device, with no more than 600 mm of pipe between the valve outlet and the tundish. That 600 mm is a maximum, and it holds however many valves discharge into the same pipe. Any discharge must be visible at the tundish.

D2: tundish to termination

Below the tundish: at least 300 mm of vertical pipe before any elbow or bend, and then a continuous fall of at least 1 in 200.

The material must be metal, or another material demonstrated to withstand the temperature of the discharge and permanently marked to identify it. That matters because the pipe must support the quick flow of very hot water to a safe termination without deforming or failing.

Size comes from the resistance table: at least one pipe size larger than the nominal outlet of the safety device, unless the total resistance exceeds that of a 9 m straight pipe — then go up a size for each further 9 m band. Bends count.

Valve outletD1D2 from tundishMaximum straight lengthResistance of each elbow
G½15 mm22 mmup to 9 m0.8 m
28 mmup to 18 m1.0 m
35 mmup to 27 m1.4 m
G¾22 mm28 mmup to 9 m1.0 m
35 mmup to 18 m1.4 m
42 mmup to 27 m1.7 m

Worked example. A G½ valve, a 10 m run and five elbows.

Try 22 mm: allowed 9 m, less five elbows at 0.8 m each = 4 m, leaving 5 m. Not enough for 10.

Try 28 mm: allowed 18 m, less five elbows at 1.0 m each = 5 m, leaving 13 m. Ten metres fits, so the answer is 28 mm.

Where one common discharge pipe serves more than one system, it is at least one size larger than the largest individual pipe joining it.

Units, packages and who may fit one

Any unvented system up to 500 litres and less than 45 kW must be a proprietary unit or package satisfying an appropriate standard such as BS EN 12897. Over 500 litres, systems are bespoke and designed to the same safety requirements by an appropriately qualified engineer.

The difference between the two words is examinable. A unit arrives with all the components already factory fitted. A package arrives with the safety devices factory fitted to the vessel and the rest supplied separately as a kit. So on a package the temperature relief valve is always factory fitted — it must be, and must never be relocated — while the expansion valve, strainer, reducing valve and check valve come loose for the installer to fit.

Each unit or package is indelibly marked with the manufacturer's details, the model reference, the rated storage capacity, the operating pressure of the system and of the expansion valve, the operating data for each safety device, and the maximum primary pressure and flow temperature. That plate is where you confirm the pressures for the cylinder in front of you.

Installation is notifiable building work. The building control body must be notified before work commences — unless the installer is registered with a competent person scheme for unvented hot water, in which case they self-certify and give the occupier a certificate of compliance within 30 days, with a copy to the BCB.

Filling, commissioning and the first thing you look at

Commissioning is done to the manufacturer's installation instructions, and the sequence is fixed:

  1. Visually inspect all connections and pipework before filling.
  2. Close all drain valves, open the hot taps, then slowly turn on the mains water, so air escapes as the vessel fills. Refilling after maintenance is the same.
  3. Set and prove the controls, and test the relief valves using the test lever, checking each reseats.

The Benchmark checklist records the safety-critical facts: installer details, that the T&P relief valve is installed and has been tested, and that the discharge pipework has been tested. A satisfied customer, an insurance document or a delivery note is not a commissioning record.

Some rules of order worth memorising: on a reported fault in an occupied property, talk to the end user first. The first activity when maintaining an unvented system is to look for signs of discharge at the tundish. Before any repair, isolate the electrical supply at the local fused spur and prove it dead. To drain the vessel, open a hot tap so air can enter. And never use uncontrolled solid fuel as the heat source for an indirect unvented system — you cannot switch off a fire that is already burning.

Not every complaint is a control fault. A creak from beneath a timber floor whenever hot water is drawn is copper expanding in a joist notch with no allowance made for movement.

🔢 The numbers worth memorising

Independent safety devices required
two, in addition to the control thermostat
Control thermostat
60 to 65 °C — a functional control
Energy cut-out
about 85 °C, non-self-resetting
Temperature relief valve
90 to 95 °C, full bore by 95 — factory fitted, never relocated
T&P valve required above
15 litres capacity
D1 size
not less than the nominal outlet of the safety device
Valve to tundish
no more than 600 mm
Below the tundish
at least 300 mm vertical before any bend, then 1 in 200 fall
D2 base size
at least one size larger than the valve outlet
Competent person certificate
to the occupier within 30 days

⚠️ Where people go wrong

  • Counting the expansion relief valve as one of the two safety devices. It does a safety job against pressure, but it is listed with the functional controls; the two Approved Document G requires are the energy cut-out and the temperature relief valve.
  • Relocating a temperature relief valve to a nearby fitting. It is factory fitted directly on the vessel.
  • Measuring D2 in straight metres and ignoring the bends. Each elbow eats 0.8 to 1.7 m of the allowance.
  • Fitting more than 600 mm of pipe between the valve and the tundish.
  • Running D2 uphill over an obstruction. It falls continuously at 1 in 200 all the way out.
  • Expecting the expansion valve to be factory fitted on a package. Only the safety devices are — the rest comes loose.
  • Heating an unvented cylinder with an uncontrolled solid fuel appliance. The cut-out cannot switch off a fire.
  • Draining an unvented vessel without opening a hot tap. It will not drain against a vacuum.

📝 10-Question Self-Test

Straight from the Level 3 course question bank. Click an option to see whether you got it right — the explanation appears instantly, and there is nothing to submit.

Your score: 0 / 10
Question 1 of 10
For an indirect unvented domestic hot water storage system heated by a boiler, which statement about the thermal cut-out is correct?
Question 2 of 10
Compared with the D1 pipework on an unvented hot water cylinder, how should the D2 discharge pipework be sized?
Question 3 of 10
Which of these falls outside the specific requirements that apply to unvented domestic hot water systems?
Question 4 of 10
The hot water at a kitchen sink tap is running too hot. What should be done to put this right?
Question 5 of 10
Which device on an unvented hot water cylinder discharges through the D1 pipework into a tundish?
Question 6 of 10
For a water system with a capacity of 15 litres or less, the Building Regulations requirement is met provided the installation is fitted
Question 7 of 10
On a direct vented hot water cylinder the immersion heater thermostat has failed, and its energy cut-out has failed with it. What is the likely result?
Question 8 of 10
The image shown illustrates the safety relief discharge pipework arrangement for an unvented hot water storage vessel. What is the maximum dimension marked A?
The drawing this question refers to
Question 9 of 10
Providing an unvented point-of-use heater serving a localised hot water outlet is non-notifiable work under the Building Regulations provided its storage capacity is no more than what?
Question 10 of 10
Every unvented hot water storage system has three levels of safety control. Which combination is required?
← Previous in Hot water systemsThe Unvented Inlet Group: Why the Order Is Fixed, and Where the Expansion Goes Next in Hot water systems →At the Outlet: Specialist Taps, Shower Pumps, Accumulators and Shock Arrestors

Going further: the lessons behind this article

This article is the public answer. Unit 332 of the Level 3 course takes the same ground to the depth the exam and the synoptic assignment ask for, in 3 lessons:

  • Three levels of safety on an unvented cylinder
  • Discharge pipework: the tundish, D1 and D2
  • Units, packages, approval and commissioning records