A caretaker reports that the basement booster set runs for a moment, stops, and starts again a few seconds later, all day long. The pumps are fine. The fault is in the vessel beside them.

The short answer

Booster pumps are centrifugal — horizontal single-stage, or on a booster set usually vertical multi-stage, where several impellers in a column each add pressure to the last (BS 8558 Annex A.6). They are installed as duplicate pumps, two or more in parallel, sized so that peak demand is still met if one pump fails.

There is no dedicated standby. The controls rotate the starting sequence so every pump takes its turn as lead, because a pump that never runs holds stagnant water and can seize. That is the answer to the site foreman's question about keeping the second one as a spare.

What sets the pump duty

How a pump duty is worked out, with a worked power calculation
Static lift, friction and residual pressure β€” then the power follows.
Key figures for booster sets
The examinable numbers from this article, in one place.

Three things (BS 8558 A.6):

Pumps and pipes are also sized to limit water hammer from surge when the set starts and stops.

The worked example the exam uses

Water is pumped to a storage cistern at 4 kg/s through a total pipe length, fittings included, of 30 m. The pump is 80 per cent efficient.

Hydraulic power = mass flow × g × head = 4 × 9.81 × 30 = 1,177 W.

The pump turns only 80 per cent of the power it takes into water power, so divide by the efficiency: 1,177 ÷ 0.8 = 1,472 W. Specify at least a 1.5 kW pump.

The step people drop is the second one. Dividing by efficiency makes the answer bigger, not smaller — a pump has to take in more than it delivers.

Packaged or self-assembled

A booster set is normally a factory-assembled package: pumps, manifolds, a control panel that starts and stops them in sequence, and a pressure accumulator, all on one skid and pre-wired, leaving only the final plumbing and electrical connections.

On a diagram of an integrally controlled booster pump, the small sensor on the discharge is the transducer and the vessel beside the pump is the accumulator.

A self-assembled set builds the same thing from separate parts — pumps, non-return valves, isolating valves, gauges, pressure switches, a pressure vessel and, with a pneumatic vessel, an air compressor. The installer then carries the responsibility for matching the vessel to the pumps and setting the switch pressures.

Either way, a Bourdon pressure gauge on the inlet and on the outlet of the pumps shows whether a pump is performing. If the outlet does not show the expected rise while the pump is called, it is not delivering.

Why the vessel exists, and the caretaker's fault

Where a boosted supply serves outlets on several floors, level switches are impractical, so the pumps are controlled by pressure — and a vessel stops them cycling.

A pneumatic pressure vessel holds a small reservoir of water under a cushion of compressed air. The pumps top up the water; the air holds the system at its design pressure while the pumps are idle. Its principal purpose is to stop the pump set cycling on and off for short periods.

It is sized on the pump flow rate, the cut-in and cut-out pressures, and the permitted number of pump starts per hour. The usable volume between the two pressures follows Boyle's law. Exam questions often shorten this to "system volume and operating pressure".

Do not confuse it with the expansion vessel on an unvented hot water system, which is sized on the volume of water heated and holds at least 4 per cent of it (BS EN 806-2 clause 10.4). Different job, different calculation.

The pre-charge is the air pressure in the empty vessel, set to 90 per cent of the pump cut-in pressure (80 to 90 per cent is the working range) so a little water always remains and the bladder never collapses. Set it wrong and the vessel holds almost no usable water between cut-out and cut-in, so every draw-off empties it at once.

That is the caretaker's set. A pump that cuts out and restarts a few seconds later has an incorrect pre-charge. Its cousin, a set that simply keeps switching on and off, has an accumulator that has lost its pressure altogether. Both are cured at the air valve, not at the pump.

Which switch does what β€” and which one failed

Every switch on the set either starts the pumps or stops them.

A pressure switch is a diaphragm working contacts at a set pressure. The low pressure switch gives the cut-in: as water is drawn and pressure falls to its setting, it starts the pumps. The high pressure switch gives the cut-out: once the system pressure is reached, it switches them off.

So a pump that has been running normally but no longer starts when water is drawn has probably lost its low pressure switch. A pump that will not stop points at the high one.

A transducer senses the same thing electronically, converting pressure into a voltage the panel reads. With a continuous signal the panel can vary pump speed to hold the pressure steady, run the compressor, or trip on over-pressure. On a mains-boosting set with no cistern, the transducer is the only thing that can call the pumps.

A float switch makes or breaks a circuit to remote equipment, and on a booster system it does two different jobs in two places:

On a silent set: a half-empty high-level cistern with the pumps not called points to its float switch or circuit. A nearly empty break cistern means the dry-run switch has done its job, and the fault is upstream in the cistern feed.

Working on the set safely

Isolate the electrical supply, prove dead and lock off. Before removing a gauge, confirm the section of pipe is fully drained.

BS EN 806-5 Annex A lists a pressure booster pump for attention once a year, serviced to the manufacturer's instructions. The annual service checks the vessel pre-charge and cleans the filters, and a visual inspection confirms the cistern water level is correct. After planned maintenance the whole installation — pumps, pipework and vessels — is flushed with clean water introduced at the break cistern before it returns to service (BS 8558 clause 5.2.3.1).

🔢 The numbers worth memorising

Pump type
centrifugal β€” usually vertical multi-stage on a booster set
Duplication
sized so peak demand is met with one pump out, with a rotating lead
Pump duty
static lift + friction losses + residual pressure
Power
mass flow Γ— 9.81 Γ— head, divided by efficiency
Worked example
4 Γ— 9.81 Γ— 30 = 1,177 W Γ· 0.8 = 1,472 W β†’ a 1.5 kW pump
Vessel pre-charge
90 per cent of cut-in (80–90 per cent working range)
Vessel sizing
pump flow rate, cut-in and cut-out pressures, permitted starts per hour
Service interval
once a year (BS EN 806-5 Annex A)

⚠️ Where people go wrong

  • Multiplying by the efficiency instead of dividing. A pump takes in more than it delivers, so the figure goes up.
  • Keeping one pump as an untouched standby. A pump that never runs holds stagnant water and seizes β€” the sequence rotates for a reason.
  • Blaming the pumps for short-cycling. A restart within seconds is an incorrect pre-charge, cured at the air valve.
  • Confusing the booster vessel with an unvented expansion vessel. Different sizing basis entirely.
  • Diagnosing β€œno water at the top” without asking which cistern is empty. A low break cistern means the dry-run switch worked and the fault is upstream.
  • Flushing after maintenance from anywhere but the break cistern.

📝 10-Question Self-Test

Straight from the Level 3 course question bank. Click an option to see whether you got it right — the explanation appears instantly, and there is nothing to submit.

Your score: 0 / 10
Question 1 of 10
A pressure switch is fitted on the inlet side and another on the outlet side of a device so that its performance can be monitored. What is the device?
Question 2 of 10
Mains-boosting pumps are installed on a system that has no storage cistern of any kind. What sends the pumps the signal to run?
Question 3 of 10
The pre-charge in a pneumatic vessel is found to be wrong. To what pressure should it be re-charged?
Question 4 of 10
A boosted cold water system has a low-level break cistern and a high-level storage cistern. The pump appears to have seized after 'running dry' for a while. Which control is most likely to have failed and let this happen?
Question 5 of 10
Which one of these components switches the pump on and off?
Question 6 of 10
On the image, what is the component labelled number 6?
The drawing this question refers to
Question 7 of 10
In the image below, which component keeps the system pressurised while the pump is not running?
The drawing this question refers to
Question 8 of 10
Which component makes use of compressed air to cut down the number of times the pump cycles?
Question 9 of 10
In the system shown, which component switches the pump off once the required system pressure has been reached?
The drawing this question refers to
Question 10 of 10
Which components are used to check that a booster pump is performing as it should?
← Previous in Cold water systemsCisterns in Tall Buildings: the Mains Limit, the Break Cistern and the 50 mm Stack Next in Cold water systems →Private Water Supplies: Boreholes, Springs, Treatment and the Three House Layouts

Going further: the lessons behind this article

This article is the public answer. Unit 331 of the Level 3 course takes the same ground to the depth the exam and the synoptic assignment ask for, in 2 lessons:

  • Booster sets: duplicate pumps, packaged units and annual servicing
  • Booster sets: the pressure vessel and the control switches