Two figures decide whether the top-floor shower will ever work, and no drawing gives either of them. Both are measured on site, before the calculation starts.

The short answer

Strip away every design factor and one question is left: what flow does the installation require, against what the supply can deliver? Every other decision follows from the gap between those two numbers.

So the sizing runs in one direction: measure what the supply gives → count the loading units the building wants → pick a pipe size from the table → and where the supply cannot meet the demand, add a pump or an accumulator.

Measuring what the supply gives

A small isolating service valve
A service valve at every appliance, so one repair does not drain the building.
Key figures for sizing a cold water system
The examinable numbers from this article, in one place.

For a cistern-fed system, the pressure available at an outlet is the vertical distance from the base of the cistern to the outlet (the older BS 6700 method took it from the cistern outlet). Pressure is expressed as head: 10 m of head is roughly 1 bar (100 kPa).

For a mains-fed system the figure is the minimum pressure at peak demand, read with a pressure gauge on an outside tap at a busy time of day, or obtained from the undertaker. A reading taken at a quiet time flatters the main and the shower pays for it later.

The second figure is the flow rate, measured with a weir gauge: water escapes through a slot in the side and the height it reaches reads the flow. A weir gauge reads flow rate and nothing else — not pressure loss, not head loss, not diameter — and excessive flow spills over the top and gives a false reading, so use a flow meter on a strong supply.

Putting the measurements together. A 1:50 floor plan shows the cold supply to a bathroom as a line 184 mm long: 184 × 50 = 9,200 mm, so 9.2 m horizontally. The section shows the bathroom floor 2.7 m above the stop valve. The actual pipe length is 9.2 + 2.7 = 11.9 m, which sets the friction loss — and the 2.7 m rise is deducted from the available head, because the water has to climb it before it reaches the tap. The rise gets counted twice, for two different reasons, and that is the step people miss.

Loading units

Loading units and design flow rates for common appliances
One loading unit is 0.1 l/s. Everything else is built off that.

Three related figures. The design flow rate is what an outlet should get when it is the only one discharging. The minimum flow rate is what it must still get when other outlets are in simultaneous use. A loading unit (LU) is a number given to an appliance allowing for its flow rate, how long it runs and how often it is used — and one loading unit equals 0.1 l/s.

Draw-off pointDesign flowMinimumLU
Washbasin, handbasin, bidet, WC cistern0.1 l/s0.1 l/s1
Kitchen sink, washing machine, dishwasher, shower head0.2 l/s0.15 l/s2
Urinal flush valve0.3 l/s0.15 l/s3
Bath (domestic)0.4 l/s0.3 l/s4
Garden or garage tap0.5 l/s0.4 l/s5

Older material and BS 8558 Table 5 carry the BS 6700 figures instead (WC 0.13, basin 0.15, bath 0.30, sink 0.20). If a question asks for the design flow rates used for pipe sizing, give the BS EN 806-3 set.

One refinement: where a mixer is fed from both hot and cold, the demand is shared, so about 70 per cent of the tabulated rate is allowed on each side. Adding the hot and cold loading units together oversizes the pipe (BS 8558 clause 4.3.30).

Cistern storage

BS EN 806-2 clause 19.1.4: for a dwelling with a constant supply at adequate pressure, a maximum of 80 litres per person normally resident should prove satisfactory; where the cistern refills only at night, base it on 130 litres per person. Table 6 covers other buildings — hostel 90 l per bed, hotel 200 l per bed, office 45 l per employee, primary school 15 l per pupil.

Two rules of thumb from the withdrawn BS 6700 are still asked for: a cistern feeding only the hot water cylinder must hold at least the capacity of the cylinder; one feeding both cold outlets and the cylinder must hold at least 230 litres.

And the constraint that pulls the other way: do not oversize. BS EN 806-2 says water must be held in storage for as short a time as possible to prevent stagnation.

A four-person house: 4 × 80 = 320 litres, comfortably above the 230 litre minimum for a cistern serving both. Night-only refilling would give 520.

The copper table, worked

BS EN 806-3 Table 3.2 for copper reads like this:

Copper tubeMaximum loadHighest single applianceMaximum length
12 mm1 / 2 / 3 LU2 LU20 m / 7 m / 5 m
15 mm3 / 4 / 6 LU4 LU15 m / 9 m / 7 m
18 mm10 LU5 LUno limit
22 mm20 LU8 LUno limit
28 mm50 LU—no limit

Read the small sizes with their length limits: 15 mm carries 4 LU only up to 9 m, and 6 LU only up to 7 m. The "highest single appliance" column stops a bath (4 LU) being fed through a size that only allows a 2 LU appliance. Going up a size is always permitted.

The worked house. Bath (4), shower (2), basin (1), WC (1), kitchen sink (2), washing machine (2) — 12 LU in total. Work back from the furthest outlet:

Where a section also feeds a storage cistern, add the cistern refill flow to that section.

Notice what never entered the calculation: the number of bends, the insulation, the warning pipe. Only the loading units each section carries, the length for the small sizes, and the biggest single appliance on the run. Three numbers per section.

When the main falls short: the pump

When to specify a pump and when to specify an accumulator
Not enough pressure and not enough flow are different faults with different answers.

The table sizes the pipe; it cannot make the main deliver. In a dwelling the pump normally draws direct from the supply pipe, which BS 8558 Annex A.4 permits where the pumped rate is not more than 0.2 l/s (12 litres per minute). Anything larger needs the undertaker's written consent and is notifiable under Regulation 5 — the same 12 l/min figure from the notification list, seen from the other end.

The pump head must cover three things (BS 8558 Annex A.6): the static lift + the friction losses + the residual pressure the appliance needs. Miss any of the three and the shower runs weak.

Worked example. The shower needs 0.2 l/s at 100 kPa (10 m head). Static lift 4 m, friction losses 3 m. Total head = 4 + 3 + 10 = 17 m.

Hydraulic power = flow × 9.81 × head = 0.2 × 9.81 × 17 = 33 W; at 60 per cent efficiency the motor must supply about 56 W.

The duty point is 0.2 l/s at 17 m. A pump chosen for 0.2 l/s at 10 m — the shower's own figure — would be seven metres of head short before it started.

When the main is slow rather than weak: the accumulator

Different problem: the main gives a healthy 2 bar but only 10 litres a minute, and the customer wants a 15 l/min shower. The main cannot keep up while the shower runs. The answer is not a bigger pump but a store that fills slowly and empties fast.

An accumulator is a vessel with a rubber bladder, pre-charged with air on one side and filled with water on the other. The air is compressed as water enters, so the stored water leaves under pressure without any pump running. The pre-charge must be below the incoming pressure or the vessel never fills; the usual rule is about half the supply pressure, with a PRV upstream to protect the bladder.

Worked example. Mains at 2 bar, 10 l/min. A 300 litre accumulator charged to 1 bar stores roughly half its volume — 150 litres. A 15 l/min shower runs 150 ÷ 15 = 10 minutes from store, and the main refills it in 150 ÷ 10 = 15 minutes.

So the vessel is sized on how long the biggest draw-off lasts and how long the main takes to put the water back, and the pre-charge decides how much of the vessel is actually water.

An expansion vessel looks the same and is not the same. It absorbs the growth in volume when water is heated — at least 4 per cent of the volume heated on an unvented heater — and it stores nothing for use.

Presenting the working

For buildings other than dwellings, the tabular method of BS 8558 Annex C is used instead of the simplified table: for each numbered section, convert loading units to design flow, assume a size, read head loss per metre and velocity off the pipe chart, add the equivalent length of fittings, and check that the residual head at the end of the section is at least what the tap needs. If not, go up a size and repeat.

Present it the way the withdrawn BS 6700 (Annex D) set out, which is still the practice: a line drawing with every junction numbered from the source, and a calculation sheet with a row per section giving loading units, design flow, pipe size, velocity, head loss, lengths, available and residual head. The numbers on the drawing are the row numbers on the sheet, so a reader can put a finger on any pipe and find its working.

What goes out depends on who reads it. A householder's quotation gets a simple sketch with the sizes marked. A tender gets the calculation sheet with scale drawings, the specification and a bill of quantities. Same twelve loading units, same 22 mm supply pipe — only the paperwork changes.

🔢 The numbers worth memorising

One loading unit
0.1 l/s
Head to pressure
10 m head ≈ 1 bar (100 kPa)
Basin / WC
0.1 l/s, 1 LU · sink, shower, machine 0.2 l/s, 2 LU
Bath
0.4 l/s, 4 LU · garden tap 0.5 l/s, 5 LU
Mixer fitting
about 70 per cent of the tabulated rate on each side
Dwelling storage
80 l per person, or 130 if it refills only at night
Cistern serving both
at least 230 litres (rule of thumb, withdrawn BS 6700)
Copper 15 mm
4 LU up to 9 m, 6 LU up to 7 m, highest single appliance 4 LU
Copper 22 mm
20 LU, highest single 8
Direct-boost limit
0.2 l/s (12 l/min) without consent
Pump head
static lift + friction losses + residual pressure — 4 + 3 + 10 = 17 m
Hydraulic power
flow × 9.81 × head, ÷ efficiency — 0.2 × 9.81 × 17 = 33 W, ≈ 56 W at 60%
Accumulator pre-charge
about half the supply pressure, PRV upstream

⚠️ Where people go wrong

  • Counting the rise once. It adds to the pipe length for friction and subtracts from the available head — two separate effects.
  • Adding a mixer’s hot and cold loading units together. About 70 per cent goes on each side, or the pipe is oversized.
  • Reading the 15 mm column without its length limit. 4 LU is only good to 9 m.
  • Specifying 18 mm because the table says so. It is not a stocked UK size — go to 22.
  • Sizing a pump at the appliance’s own head. Add the static lift and the friction, or it is short before it starts.
  • Multiplying by efficiency instead of dividing when finding motor power.
  • Oversizing a cistern for “security of supply”. Standing water stagnates, and the standard says so explicitly.
  • Confusing an accumulator with an expansion vessel. One stores water for use, one absorbs the growth of heated water.

📝 10-Question Self-Test

Straight from the Level 3 course question bank. Click an option to see whether you got it right — the explanation appears instantly, and there is nothing to submit.

Your score: 0 / 10
Question 1 of 10
The size of the distribution pipe running from a CWSC to a dwelling is decided by which one of these factors?
Question 2 of 10
Of the pipe installations listed, which would give the highest flow rate?
Question 3 of 10
The volume flow rate through a pipe is given by which formula?
Question 4 of 10
During pipe sizing, the pipe length that also allows for every fitting and component on the run is called what?
Question 5 of 10
The term 'Loading Units' takes account of which set of factors?
Question 6 of 10
A cistern is 1,000 mm x 800 mm x 700 mm. Filled to its shut-off level it holds 75% of its nominal volume. What volume of water does it hold?
Question 7 of 10
Water has to be pumped up to a storage cistern at 4 kg/s against a head of 30 m, the lift to the cistern. The pump is 80% efficient. What pump power, in watts, is needed?
Question 8 of 10
A client wants drawings to accompany your basic quotation. What type of drawing would normally be provided at this stage?
Question 9 of 10
Which building detail could be measured from a side elevation drawing?
Question 10 of 10
Why is water velocity kept as low as practicable when pipe sizes are being calculated?
← Previous in Cold water systemsWhere the Design Comes From: the Law, the Standards, and Which Drawing Answers Which Question Next in Cold water systems →Diagnosing a Cold Water Fault: Four Sources, Four Readings, and Isolating It Safely

Going further: the lessons behind this article

This article is the public answer. Unit 331 of the Level 3 course takes the same ground to the depth the exam and the synoptic assignment ask for, in 4 lessons:

  • Available pressure and flow, feed arrangements and loading units
  • Cistern sizing, float valve refill and pipe design limits
  • Pipe sizing from BS EN 806-3 tables and pump duty
  • Accumulators on a weak main and the calculation sheet